Multi-Channel Recorders

  • Capacity to store up to 300,000 interval computations in memory
  • Accept analog or event inputs with sample rates from one per second up to one every eight hours
  • Combine these units with a power source and communication option
  • Administer a network of hundreds of remote recorders throughout your municipality or across your client base

The Telog R-33xx recorders become your eyes and ears in the field. The recorders accept analog and/or event inputs with a sample rate of 1 per sec up to 1 per 8 hours, storing up to 300,000 interval computations in memory. Telog R-33xx units record output from a variety of sensors such as pressure, level, flow, pH, temperature and humidity. Combine the Telog R-33xx recorders with a power source and communication option to easily administer a network of hundreds of remote recorders.

Alarm notification for critical point monitoring is available. Each alarm event is time-stamped and stored in the recorder's wrap around memory. Backup battery packs ensure data integrity in the event of a power source failure.

Telog's R-33xx family of multi-channel remote recorders provide you with cost effective tools for gathering, understanding and managing information from your system. Designed for multiple applications, the Telog R-33xx recorders can work in a network or as solo data loggers, indoors or outdoors, battery-operated or externally powered. Support software copies the stored data for detailed analysis and professional presentations. 

 
 
BENEFITS
 
 

NEMA 4x Enclosure and IP67 Rated

All connectors and fittings are watertight and the product is environmentally rated IP67 to 3 meters of depth

Battery Operated

AC power is not needed, significantly reducing installation and maintenance costs

CellularM2M

Provided with the Telog WM/C cellular m2m modem which is certified on the Sprint and Verizon Wireless networks in the US and the Bell Mobility network in Canada

Data Backup

Data loss is not a concern because the recorder stores over 67,000 interval statistics before overwriting the oldest data with new

 

articles

Cellular data transfer is the ticket for successful pump station monitoring in Suffolk

Monitoring Progress: Nailing Down Water Hammer And Its Implications


White Papers

Automated Wireless Monitoring of Water Distribution Systems

SCADA Alternatives for Remote Monitoring


Recorder Model: Telog R-3303
Type: Multi-channel RTU (recording telemetry unit)

Recorder Channels
-- 3 Pulse/event channels

Memory   
-- Dynamically allocated among active channels: 256 Kbytes
    --- Pulse inputs: 82,500 16-bit values
    --- Event input: 27,500 events
    --- Storage: Wrap-around (first-in, first-out, FIFO) memory

Pulse/event Inputs:
-- Type: Pulse counting or event recording, user selectable
-- Input: Uncommitted contact or active logic signals
-- Excitation: 10 µA contact sensing current; 5 volt pull-up
-- Contact bounce: 3 ms maximum, software programmable bounce filter

Pulse Totalizing: 
-- Pulse rate: Low speed 100/s with bounce filter; Maximum pulses: 65,000 per interval; High speed: 20,000/s with no bounce filter
-- Totalizing interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Totals, overall and per interval 

Event Sampling
-- Event rate: 1 event/s maximum

Alarms
-- Activation: Event inputs only
-- Outputs: 2 Discrete outputs
-- Type: FET, open collector (open drain)
-- Maximum specifications: 30 VDC & 100 mA
-- Threshold: Event activated 

Power
-- Battery type: 9-volt lithium battery pack with MTA connector
-- Battery life: 8 months @ 73.4º F, with 1 sample every 5 s on all channels, no modem
-- External DC: Regulated 12 VDC; Unregulated 15-35 VDC

Communication
-- Local RS-232 (standard); Opto-isolated; 300 to 19,200 baud via 9 pin D connector
-- Optional Cellular modem | Licensed and unlicensed (Spread Spectrum) radio | IP packet data over Ethernet/Internet (eNET option)

Mechanical & Environmental
-- Clock accuracy: ±0.01%
-- Operating temperature: -4 to 140º F
-- Enclosure: Bent aluminum panel mount assembly; size: 8.5"x6.8"x2.3"
-- Options: Fiberglass, IEC IP65 NEMA 4X enclosures

Support Software
-- Telog Online (Data Hosted Solution)
-- Telog Enterprise
-- Telogers for Windows


Recorder Model: Telog R-3307
Type: Multi-channel RTU (recording telemetry unit)

Recorder Channels
-- 3 Pulse/event channels
-- 4 Analog

Memory   
-- Dynamically allocated among active channels: 256 Kbytes
    --- Analog inputs only: 110,000 12-bit values
    --- Pulse inputs only: 82,500 16-bit values
    --- Event inputs only: 27,500 events
    --- Storage: Wrap-around (first-in, first-out, FIFO) memory

Analog Inputs:
-- Type: Selectable using software
      --- Voltage: Bipolar or unipolar 100 mV, 200 mV, 500 mV, 1, 2, 5, 10, or 20 V full scale, or unipolar 1 to 5 V
     --- Current: Bipolar or unipolar 1 or 20 mA full scale or unipolar 4-20 mA
-- Excitation: +5 volt only; specify 3307A-E5
-- Resolution: 12 bits (0.025% of full scale)
-- Accuracy: ±0.15% (at 73.4º F), ±50 ppm/ºF

Analog Sampling
-- Sample rate: 1/sec to 1/8 hours for each channel
-- Sample interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Minimum, average and/or maximum per interval
-- Totalizers: 1 Gbyte totalizer per channel

Pulse/event Inputs
-- Type: Pulse counting or event recording, user selectable
-- Input: Uncommitted contact or active logic signals
-- Excitation: 10 µA contact sensing current; 5 volt pull-up
-- Contact bounce: 3 ms maximum, software programmable bounce filter

Pulse Totalizing: 
-- Pulse rate: Low speed 100/s with bounce filter; Maximum pulses: 65,000 per interval; High speed: 20,000/s with no bounce filter
-- Totalizing interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Totals, overall and per interval

Event Sampling
-- Event rate: 1 event/s maximum
-- Values saved: Event with time stamp (in mm:dd:yy:hh:mm:ss format), and computed run time.

Alarms
-- Activation: Analog and event inputs only
-- Outputs: 2 Discrete outputs
-- Type: FET, open collector (open drain)
-- Maximum specifications: 30 VDC & 100 mA
-- Threshold: Software programmable threshold exceedance on analog channels (high, high-high, low, low-low); event activated on event channels

Alarm Logging
-- Trigger: Logging of analog channel triggered by inputs from analog or event channels
-- Pre-trigger buffer: 0 to 5 intervals
-- Post-trigger buffer: 0 to 50 intervals

Power
-- Battery type: 9-volt lithium battery pack with MTA connector
-- Battery life: 6 months @ 73.4º F, with 1 sample every 5 s on all channels, no modem
-- External DC: Regulated 12 VDC; Unregulated 15-35 VDC

Communication
-- Local RS-232 (standard); Opto-isolated; 300 to 19,200 baud via 9 pin D connector
-- Optional Cellular modem | Licensed and unlicensed (Spread Spectrum) radio | IP packet data over Ethernet/Internet (eNET option)

Mechanical & Environmental
-- Clock accuracy: ±0.01%
-- Operating temperature: -4 to 140º F
-- Enclosure: Bent aluminum panel mount assembly; size: 8.5"x6.8"x2.3"
-- Options: Fiberglass, IEC IP65 NEMA 4X enclosures

Support Software
-- Telog Online (Data Hosted Solution)
-- Telog Enterprise
-- Telogers for Windows


Recorder
Model: Telog R-3308
Type: Multi-channel recorder

Recorder Channels
-- 3 Pulse/event channels
-- 5 Analog

Memory
-- Dynamically allocated among active channels: 256 Kbytes
   --- Analog inputs only: 122,800 12-bit values
    --- Pulse inputs only: 92,000 16-bit values
    --- Event inputs only: 30,700 events
    --- Storage: Wrap-around (first-in, first-out, FIFO) memory

Analog Inputs:
-- Type: Selectable using software
     --- Voltage: Bipolar or unipolar 100 mV, 200 mV, 500 mV, 1, 2, 5, 10, or 20 V full scale, or unipolar 1 to 5 V
     --- Current: Bipolar or unipolar 1 or 20 mA full scale or unipolar 4-20 mA
     --- Ambient temperature: AT-4 probe, -4 to 140ºF
     --- RTD: 100 ohm Pt, alpha=0.00385, 3- or 4-wire, -328º to 1472ºF
     --- Thermocouple: 2-wire, types J, K, T, E or R
-- Excitation: For voltage and current transmitters, programmable 5 or 12 volts, programmable excitation on time for 5 ms to 500 ms
-- Resolution: 12 bits (0.025% of full scale)
-- Accuracy: ±0.15% (at 73.4º F), ±50 ppm/ºF

Analog Sampling
-- Sample rate: 1/sec to 1/8 hours for each channel
-- Sample interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Minimum, average and/or maximum per interval
-- Totalizers: 1 Gbyte totalizer per channel

Pulse/event Inputs
-- Type: Pulse counting or event recording, user selectable
-- Input: Uncommitted contact or active logic signals
-- Excitation: 10 µA contact sensing current; 5 volt pull-up
-- Contact bounce: 3 ms maximum, software programmable bounce filter

Pulse Totalizing: 
-- Pulse rate: Low speed 100/s with bounce filter; Maximum pulses: 65,000 per interval; High speed: 20,000/s with no bounce filter
-- Totalizing interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Totals, overall and per interval

Event Sampling
-- Event rate: 1 event/s maximum
-- Values saved: Event with time stamp (in mm:dd:yy:hh:mm:ss format), and computed run time | Event with time stamp (in mm:dd:yy:hh:mm:ss format), and computed hi run time and lo run time

Alarms
-- Activation: Analog and event inputs only
-- Outputs: 2 Discrete outputs
-- Type: FET, open collector (open drain)
-- Maximum specifications: 30 VDC & 100 mA
-- Threshold: Software programmable threshold exceedance on analog channels (high, high-high, low, low-low); event activated on event channels

Power
-- Battery type: 9-volt lithium battery pack with MTA connector
-- Battery life: 5 months @ 73.4º F, with 1 sample every 5 s on all channels, no modem, with excitation 15 ms delay, 15 mA/sensor or channel
-- External DC: Regulated 12 VDC; Unregulated 15-35 VDC

Communication
-- Local RS-232 (standard); Opto-isolated; 300 to 19,200 baud via 9 pin D connector
-- Optional Cellular modem | Licensed and unlicensed (Spread Spectrum) radio | IP packet data over Ethernet/Internet (eNET option)

Mechanical & Environmental
-- Clock accuracy: ±0.01%
-- Operating temperature: -4 to 140º F
-- Enclosure: Bent aluminum panel mount assembly; size: 8.5"x6.8"x2.3"
-- Options: Fiberglass, IEC IP65 NEMA 4X enclosures

Support Software
-- Telog Online (Data Hosted Solution)
-- Telog Enterprise
-- Telogers for Windows


Recorder Model: Telog R-3314
Type: Multi-channel RTU (recording telemetry unit)

Recorder Channels
-- 6 Pulse/event channels
-- 8 Analog

Memory
-- Dynamically allocated among active channels: 512 Kbytes
    --- Analog inputs only: 294,300 12-bit values
    -- Pulse inputs only: 227,000 16-bit values
    -- Event inputs only: 73,600 events
    -- Storage: Wrap-around (first-in, first-out, FIFO) memory

Analog Inputs:
-- Type: Selectable using software
      -- Voltage: Bipolar or unipolar 100 mV, 200 mV, 500 mV, 1, 2, 5, 10, or 20 V full scale, or unipolar 1 to 5 V
     -- Current: Bipolar or unipolar 1 or 20 mA full scale or unipolar 4-20 mA
-- Resolution: 12 bits (0.025% of full scale)
-- Accuracy: ±0.15% (at 73.4º F), ±50 ppm/ºF

Analog Sampling
-- Sample rate: 1/sec to 1/8 hours for each channel
-- Sample interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Minimum, average and/or maximum per interval
-- Totalizers: 1 Gbyte totalizer per channel

Pulse/event Inputs
-- Type: Pulse counting or event recording, user selectable
-- Input: Uncommitted contact or active logic signals
-- Excitation: 10 µA contact sensing current; 5 volt pull-up
-- Contact bounce: 3 ms maximum, software programmable bounce filter

Pulse Totalizing: 
-- Pulse rate: Low speed 100/s with bounce filter; Maximum pulses: 65,000 per interval; High speed: 20,000/s with no bounce filter
-- Totalizing interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Totals, overall and per interval

Event Sampling
-- Event rate: 1 event/s maximum
-- Values saved: Event with time stamp (in mm:dd:yy:hh:mm:ss format), and computed run time | Event with time stamp (in mm:dd:yy:hh:mm:ss format), and computed hi run time and lo run time

Alarms
-- Activation: Analog and event inputs only
-- Outputs: 4 Discrete outputs
-- Type: FET, open collector (open drain)
-- Maximum specifications: 30 VDC & 100 mA
-- Threshold: Software programmable threshold exceedance on analog channels (high, high-high, low, low-low); event activated on event channels

Alarm Logging
-- Trigger: Logging of analog channel triggered by inputs from analog or event channels
-- Pre-trigger buffer: 0 to 5 intervals
-- Post-trigger buffer: 0 to 50 intervals

Power
-- Battery type: 9-volt lithium battery pack with MTA connector
-- Battery life: 6 months @ 73.4º F, with 1 sample every 5 s on all channels, no modem
-- External DC: Regulated 12 VDC; Unregulated 15-35 VDC

Communication
-- Local RS-232 (standard); Opto-isolated; 300 to 19,200 baud via 9 pin D connector
-- Optional Cellular modem | Licensed and unlicensed (Spread Spectrum) radio | IP packet data over Ethernet/Internet (eNET option)

Mechanical & Environmental
-- Clock accuracy: ±0.01%
-- Operating temperature: -4 to 140º F
-- Enclosure: Bent aluminum panel mount assembly; size: 8.2"x9.9"x2.3"
-- Options: Fiberglass, IEC IP65 NEMA 4X enclosures

Support Software
-- Telog Online (Data Hosted Solution)
-- Telog Enterprise
-- Telogers for Windows


Recorder
Model: Telog R-3330
Type: Multi-channel recorder

Recorder Channels
-- 6 Pulse/event channels
-- 8 Analog
-- 16 Alarm/event

Memory
-- Dynamically allocated among active channels: 1024 Kbytes
   --- Analog inputs only: 614,000 12-bit values
    --- Pulse inputs only: 459,000 16-bit values
    --- Event inputs only: 152,995 events
    --- Storage: Wrap-around (first-in, first-out, FIFO) memory

Analog Inputs:
-- Type: Selectable using software
     --- Voltage: Bipolar or unipolar 100 mV, 200 mV, 500 mV, 1, 2, 5, 10, or 20 V full scale, or unipolar 1 to 5 V
     --- Current: Bipolar or unipolar 1 or 20 mA full scale or unipolar 4-20 mA
-- Resolution: 12 bits (0.025% of full scale)
-- Accuracy: ±0.15% (at 73.4º F), ±50 ppm/ºF

Analog Sampling
-- Sample rate: 1/sec to 1/8 hours for each channel
-- Sample interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Minimum, average and/or maximum per interval
-- Totalizers: 1 Gbyte totalizer per channel

Pulse/event Inputs
-- Type: Pulse counting or event recording, user selectable
-- Input: Uncommitted contact or active logic signals
-- Excitation: 10 µA contact sensing current; 5 volt pull-up
-- Contact bounce: 3 ms maximum, software programmable bounce filter

Pulse Totalizing: 
-- Pulse rate: Low speed 100/s with bounce filter; Maximum pulses: 65,000 per interval; High speed: 20,000/s with no bounce filter
-- Totalizing interval: 1 s to 8 h, synchronized to the hour, channel independent
-- Values saved: Totals, overall and per interval

Event Sampling
-- Event rate: 1 event/s maximum
-- Values saved: Event with time stamp (in mm:dd:yy:hh:mm:ss format), and computed run time | Event with time stamp (in mm:dd:yy:hh:mm:ss format), and computed hi run time and lo run time

Alarm/Event Inputs
-- Type: Event recording only
-- Input: Uncommitted contact or active logic signals
-- Excitation: 10 µA contact sensing current; 5 volt pull-up
-- Contact bounce: 3 ms maximum, software programmable bounce filter

Alarms
-- Activation: Analog and event inputs only
-- Outputs: 2 Discrete outputs
-- Type: FET, open collector (open drain)
-- Maximum specifications: 30 VDC & 100 mA
-- Threshold: Software programmable threshold exceedance on analog channels (high, high-high, low, low-low); event activated on event channels

Power
-- Battery type: 9-volt lithium battery pack with MTA connector
-- Battery life: 4 months @ 73.4º F, with 1 sample every 5 s on all channels, no modem
-- External DC: Regulated 12 VDC; Unregulated 15-35 VDC

Communication
-- Local RS-232 (standard); Opto-isolated; 300 to 19,200 baud via 9 pin D connector
-- Optional Cellular modem | Licensed and unlicensed (Spread Spectrum) radio | IP packet data over Ethernet/Internet (eNET option)

Mechanical & Environmental
-- Clock accuracy: ±0.01%
-- Operating temperature: -4 to 140º F
-- Enclosure: Bent aluminum panel mount assembly; size: 8.2"x9.9"x2.3"
-- Options: Fiberglass, IEC IP65 NEMA 4X enclosures

Support Software
-- Telog Online (Data Hosted Solution)
-- Telog Enterprise
-- Telogers for Windows


Meters, Sensors, Options
 

Telog-supported Flowmeters

Flow meters via RS-232 or RS-485 interface to meter serial interface port:

  • Hach Sigma series
  • ISCO 2150 Laser & Signature Logger
  • Marsh McBirney Flo-Dar & Flo Tote3
  • Teledyne MGD ADFM & accQmin
  • ADS Flowshark & Triton
  • FloWav area velocity sensor

Telog-supplied Meters & Sensors

  • Utrasonic sensor
  • Pressure sensor
  • Temperature sensor
  • pH sensor
  • Rain Gauge

Water Quality

  • Hach Hydrolab multiparameter Sondes
  • DataSonde 4a, MiniSonde 4a
  • DSSX, DSS, MXX
  • Hach WDM Pipe Sonde
 
 

Get the Telog Multi-Channel

Request a Quote